Gas Monitoring Program


1.0 INTRODUCTION

1.1 Goal
1.2 Scope

2.0 PROCEDURES

2.1 Monitoring Requirements
2.1.1 Highly Toxic Gases
2.1.2 Toxic Gases
2.1.3 Flammable Gases
2.1.4 Pyrophoric Gases
2.2 Location of Monitoring Sensors
2.3 Continuous Versus Temporary Monitoring System
2.4 Gas Monitoring Responsibility
2.5 Gas Alarm Set Points
2.6 Action Triggered by Monitoring Alarm
2.7 Alarm Annunciation
2.8 Compatibility Requirements

3.0 RESPONSIBILITIES

3.1 Management
3.2 Physical Plant and Campus Police
3.3 Industrial Hygiene and Safety

4.0 REFERENCES


1.0 INTRODUCTION

Requirements for gas monitoring apply to the use of any highly toxic, toxic, flammable, and/or pyrophoric gases. Plans to purchase monitoring equipment must be reviewed and approved by the Industrial Hygiene Section of the NCSU Environmental Health and Safety Center.

1.1 Goal

This program outlines the requirements and responsibilities necessary to provide suitable gas monitoring systems. The goal is to assure standardization of set points, calibration of monitors, and uniform response to alarms such as positive gas flow shutdown when certain set points are exceeded. This document also encompasses annunciation requirements to assure emergency response personnel need not enter the danger zone to ascertain the status of alarms.

1.2 Scope

This procedure applies to all use of compressed gases other than short term use of limited quantities of compressed gases in a chemical fume hood. Fume hood applications involving hazardous gases shall be reviewed by the NCSU Environmental Health and Safety Center.

2.0 PROCEDURES

2.1 Monitoring Requirements

2.1.1 Highly Toxic Gases

Highly toxic gases include:

These gases shall be monitored by a continuous monitor except when the cylinder highly toxic gas concentration (in ppm) is less than the National Institute for Occupational Safety and Health (NIOSH) Immediately Dangerous to Life and Health (IDLH) level. If an IDLH is not available for the chemical and the cylinder concentration is greater than the Occupational Safety and Health Administration (OSHA) Permissible Exposure Value (PEL), the Principal Investigator and NCSU Industrial Hygiene representative shall determine the need for continuous monitoring. Continuous monitoring is defined as gas detection by the monitor at any sampling point within 30 seconds at ½ the TLV.

Examples: Arsine, diborane, germane, phosphine, nitric oxide, methyl bromide, boron trifluoride, chlorine, chlorine trifluoride, dichlorosilane, hydrogen fluoride, nitrogen dioxide, phosgene, sulfur tetrafluoride.

Highly toxic gases are exempt from continuous monitoring if the gas quantity is limited to 500 cc of gas phase by volume in a lecture bottle or sample cylinder, a flow restricting orifice is installed in the CGA fitting and:

2.1.2 Toxic Gases

Toxic gases include:

Toxic gases shall be monitored by a continuous monitor except when the cylinder toxic gas concentration is less than the National Institute for Occupational Safety and Health (NIOSH) Immediately Dangerous to Life or Health (IDLH) level. If an IDLH is not available for the chemical and the concentration is greater than the Occupational Safety and Health Administration (OSHA) Permissible Exposure Value (PEL), the laboratory Principal Investigator and NCSU Industrial Hygiene representative shall determine the need for continuous monitoring.

Examples: Ammonia, boron trichloride, boron trifluoride, carbon monoxide, carbonyl sulfide, ethyl chloride, hydrogen bromide, hydrogen chloride

Toxic gases are exempt from continuous monitoring if the cylinder contains less than 100 grams of material, the cylinder valve has a CGA fitting and

2.1.3 Flammable Gases (non-toxic or corrosive)

Flammable gases include:

These gases shall be monitored by a continuous monitor except when the cylinder contains less than or equal to 10 cubic feet of gas by volume or: Natural gas plumbed as a "house gas" need not be monitored by continuous monitoring in the lab. It is strongly recommended that flammable gas monitors calibrated for hydrogen respond to 5% of the LEL (warn, see 2.5) and 10% of the LEL (alarm). Flammable gas detectors which respond to very low ppm concentration are not required nor recommended.

Examples: Hydrogen Acetylene, Propane

2.1.4 Pyrophoric Gases

Pyrophoric gases include:

Gases that shall be monitored by a continuous monitor except when the cylinder gas concentration is below the pyrophoric limit for that gas (for example, 2 % or less silane or disilane).

If the following conditions are met, pyrophoric gases are exempt from monitoring.

These gases will almost always ignite spontaneously in contact with air at a temperature of 130 degree F (54.4C) or below (29CFR1200).

Examples: Silane, disilane

2.2 Location of Monitoring Sensors

Highly toxic gas, toxic gas and pyrophoric gas monitoring requires that sensing ports be located in the gas cabinet and at least each of the following locations:

Flammable: Monitoring requires at least one sensing point located in the laboratory for cylinders, e.g., monitors are not required for non-toxic flammable gas when the gas is an exhausted enclosure.

2.3 Continuous Versus Temporary Monitoring System

A continuous monitoring system is one that is permanently installed and is required to be on-line as long as the gas is in use in the laboratory. It will provide both alarms and interlock functions.

A temporary monitoring system is one that may be portable and is used only when the gas system is on-line with the person running the tool. It will only provide an alarm that is visual and audible. In this case, alarm conditions do not result in automatic gas shutdown, therefore the experiment must be continuously attended during gas use and means for remote gas shutdown must be present.

2.4 Gas Monitoring Responsibility

The person designated as being responsible for the monitors shall be identified in the Safety Plan. Procedures shall be documented for response to all monitor alarms. Contact names and numbers must by provided for on and off hour response.

2.5 Gas Alarm Set Points

When a gas is both toxic and flammable or pyrophoric, the more stringent (sensitive) monitoring requirement shall be used. Both monitors are not required.

Detectors shall provide constant visual detection level readout with the following alarm set points established:

Gas detected in contained/exhausted enclosures* 1/2 TLV for 4 seconds
* All gases shutdown in lab
* Evacuate lab (local alarm)
Gas detected in ambient/breathing air locations* 1/2 TLV for 4 seconds
* All gases shutdown in lab
* Evacuate building (building alarm)

2.6 Action Triggered by Monitoring Alarm

The following items shall be included in the actions taken when a local alarm or building alarm is triggered:

2.7 Alarm Annunciation

2.8 Compatibility Requirements

3.0 RESPONSIBILITIES

3.1 Management

The owning manager of the tool/process/experiment requiring gas monitoring per this procedure shall ensure the following areas are addressed:

3.2 Physical Plant and Campus Police

Assure appropriate personnel are knowledgeable about building alarms.

3.3 Industrial Hygiene and Safety

The Industrial Hygiene and Safety Section is responsible for:

4.0 REFERENCES

OSHA 29CFR 1910.1200 Appendix A "Health Hazard Definition"

OSHA 49CFR 173.326 Poison A

IBM Corporate Labeling Standard

"Guide to Safe Handling of Compressed Gases" Matheson, 1983

Toxic Gas Ordinance, City of San Jose, September 27,1990

A Model Ordinance for toxic Gas Regulation, Santa Clara County - Fire

Chief's Association, November 1988

The BOCA National Fire Prevention Code/1987, Building Officials &

Code Administrators International, Inc.

Uniform Fire Code - Article 80, California Fire Chiefs Association, January 15 1987

CGS-413-02A Gas group Listing and Definitions IBM EF 1-5-90


EHSC Home
NCSU Home 

Page